Tanya via WhatsApp

Lutron DW-6095 3 Phase Power Analyzer

Share on facebook
Share on twitter
Share on linkedin
Lutron DW-6095 3 Phase Power Analyzer

Lutron DW-6095 3 Phase Power Analyzer

Alat analisa kelistrikan DW-6093SD merk Lutron dari Taiwan. Dirancang untuk mengukur nilai-nilai listrik seperti tegangan (Voltage), arus (Current), daya (Power), frekuensi (Frequency). 3p:4w dan dapat menyimpan data melalui SD Card, dapat mendownload data sebagai file Excel, yang tidak memerlukan software. Fungsi analisis daya ACV, ACA, Faktor daya, Sudut frasa, Frekuensi, Daya Aktif (Nyata), Daya Semu, Daya Reaktif, Watt Jam, Jam VA, Jam VAR, Harmonisa.

 


Produk asli Kami distributor langsung Lutron Harga murah. Pengiriman ke seluruh Indonesia.


Whatsapp :  0851 6306 9421
Email : [email protected]

 

Lutron DW-6095 3 Phase Power Analyzer

CV. Syariftama Multi Global has a wide range of Lutron products – search by type, or model, or filter by brand to find the one you are after. If you still can’t find it contact us..

Electrical analyzer DW-6093SD brand Lutron from Taiwan. Designed to measure electrical values ​​such as voltage (Voltage), current (Current), power (Power), frequency (Frequency). 3p:4w and can store data via SD Card, can download data as an Excel file, which does not require software. Power analysis functions ACV, ACA, Power factor, Phrase angle, Frequency, Active (Real) Power, Apparent Power, Reactive Power, Watt Hour, VA Hour, VAR Hour, Harmonics.

Features Lutron DW-6095 3 Phase Power Analyzer :

  • Analysis for 3 phase multi-power system, 1P/2W, 1P/3W, 3P/3W, 3P/4W.
  • 3 current probes ( CP-1201 ) are included, if change the current probes, the calibration procedures are not necessary.
  • Current probe input signal/ranges with selection :
    Input signal (ACV) : 200 mV/300 mV/500 mV/1 V/2 V/3 V.
    Ranges (ACA) : 20 A/200 A/2000 A/30 A/300 A/ 3000 A.
  • Meter can cooperate the universal current probes.
  • Complete set with 4 PCs Test Leads, 4 PCs Alligator clips, 3 PCs Clamp Probe ( CP 1201 ), AC to DC 9V adapter, 2 G SD memory card and Carrying bag.
  • Measurement :
    V (phase-to-phase), V (phase-to-ground) A (phase-to-ground)
    KW / KVA / KVAR / PF (phase)
    KW / KVA / KVAR / PF (system)
    KWH / KVAH / KVARH / PFH (system)
    Phase angle
  • Harmonics display (1-50th order).
  • Simultaneous display of Harmonics and Wave form.
  • Display of Waveform with Peak Values.
  • Analysis of Total Harmonic Distortion ( THD ).
  • Graphic Phase diagram with 3-Phase system parameters.
  • 3 phase Voltage or Current Unbalanced Ratio ( VUR, AUR ) and Unbalanced Factor.
  • Calculated Unbalanced Current through Neutral Line ( An )
  • Capture Transient events (including Dip, Swell and Outage ) with programmable threshold ( % ).
  • Programmable CT ratio ( 1 to 600 ) and PT ratio ( 1 to 1000 ).
  • ACV input impedance is 10 Mega ohms.
  • Safety Standard : IEC 1010, CAT III 600V.
  • Powered by AA ( UM-3 ) DC 1.5 V X 8 batteries ( Alkaline type ) or DC 9V adapter.
  • Computer data output, can cooperate with optional USB Cable/USB-01, RS232 cable/UPCB-02 and Data Acquisition software, SW-811.
  • Optional current probes : CP-1201, CP-2000, CP-200, CP-3000, detail specification.
  • User can order the meter only ( without the current probes ) with the special request as intend to cooperate their own current probes.
  • Patented.

Specifications Lutron DW-6095 3 Phase Power Analyzer :

Wire connections 1P:2W, 1P:3W, 3P:3W, 3P:4W
Sampling time 1 second
Data storage SD memory card
Interface RS232, USB PC interface
Functions Data hold
Clamp max. conductor size ø50 mm (CP-1201)
Clamp dimensions/ Jaw 210 x 64 x 33 mm/ 86 mm
Satety standard IEC1010 CAT III 600 V
Power requirement Battery AA x 8
Dimensions/ Weight 225 x 125 x 64 mm/ 948 g

ELECTRICAL SPECIFICATIONS:

Measurement Range Resolution Accuracy
ACV 10.0 to 600.0 V 0.1 V ± (0.5% + 0.5 V)
ACA 20 A 0.001 A, < 10 A ± (1% + 0.1 A), Meter & CP-1201
0.01 A, ≥ 10 A ± (0.5% + 0.02 A), Meter only
200 A 0.01 A, < 100 A ± (1% + 0.5 A), Meter & CP-1201
0.1 A, ≥ 100 A ± (0.5% + 0.2 A), Meter only
1200 A 0.1 A, < 1000 A ± (1% + 5 A), Meter & CP-1201
1 A, ≥ 1000 A ± (0.5% + 2 A), Meter only
Power factor 0.00 to 1.00 0.01 ± 0.04
Phase angle -180º to 180º 0.1º ± 1º
Frequency 45 to 65 Hz 0.1 Hz ± 0.1 Hz
Active (Real) Power 0.000 to 9.999 KW 0.001, 0.01, 0.1 KW ± (1% + 0.008 KW)
10.00 to 99.99 KW 0.01, 0.1 KW ± (1% + 0.08 KW)
100.0 to 999.9 KW 0.1 KW ± (1% + 0.8 KW)
1,000 to 9,999 KW 0.001 MW ± (1% + 0.008 MW)
Apparent Power 0,000 to 9,999 KVA 0.001, 0.01, 0.1 KVA ± (1% + 0.008 KVA)
10.00 to 99.99 KVA 0.01, 0.1 KVA ± (1% + 0.08 KVA)
100.0 to 999.9 KVA 0.1 KVA ± (1% + 0.8 KVA)
1,000 to 9,999 MVA 0.001 MVA ± (1% + 0.008 MVA)
Reactive Power 0.000 to 9.999 KVAR 0.001, 0.01, 0.1 LEFT ± (1% + 0.008 QUAR)
10.00 to 99.99 KVAR 0.01, 0.1 LEFT ± (1% + 0.08 KVAR)
100.0 to 999.9 KVAR 0.1 LEFT ± (1% + 0.8 REMAINS)
1,000 to 9,999 MVAR 0.001 MVAR ± (1% + 0.008 MVAR)
Watt Hour (Active Power Hour) : WH 0.000 to 9.999 KWH 0.001 KWH ± (2% + 0.008 KWH)
10.00 to 99.99 KWH 0.01 KWH ± (2% + 0.08 KWH)
100.0 to 999.9 KWH 0.1 KWH ± (2% + 0.8 KWH)
1.000 to 9.999 MHW 0.001 MWH ± (2% + 0.008 MWH)
VA Hour (Apparent Power Hour) : SH 0.000 to 9.999 KVAH 0.001 kVA ±(2%+0.008KVAH)
10.00 to 99.99 KVAH 0.01 kVA ±(2%+0.08KVAH)
100.0 to 999.9 KVAH 0.1 kVA ±(2%+0.8KVAH)
1.000 to 9.999 MVAH 0.001 MVAH ± (2% + 0.008 MVAH)
VAR Hour (Reactive Power Hour) : QH 0.000 to 9.999 KVARH 0.001 KVARH ±(2%+0.008 KVARH)
10.00 to 99.99 KVA 0.01 KVARH ±(2%+0.08KVARH)
100.0 to 999.9 KVARH 0.1 KVARH ±(2%+0.8KVARH)
1.000 to 9.999 MVARH 0.001 MVARH ± (2% + 0.008 MVARH)
Harmonics of AC voltage in Magnitude 1 to 20th 0.1 V ± (2% + 0.5 V)
21 to 30th ± (4% + 0.5 V)
31 to 50th reference
Harmonics of AC voltage in Percentage 1 to 20th 0.1% ± (2% + 10 d)
21 to 30th ± (4% + 20 d)
31 to 50th reference
Harmonics of AC current in Magenitude 1 to 20th 0.1 A ± (2% + 0.5 A)
21 to 30th ± (4% + 0.5 A)
31 to 50th reference
Harmonics of AC current in Percentage 1 to 20th 0.1% ± (2% + 10 d)
21 to 30th ± (4% + 20 d)
31 to 50th reference
Peak value of ACV or ACA 50 Hz 19 μs ± (5% + 30 d)
60 Hz 16 μs
Crest Factor of ACV or ACA 1.000 to 99.99 0.001 ± (5% + 30 d)
Total Harmonic Distortion 0 to 20% 0.1% ± (2% + 5 d)
20.1 to 100% ± (6% + 10 d)

 

 

 